Bacteria Testing for Liquid Coolant

Bacteria testing

Industrial Inspection Company’s laboratory in Monroe, Michigan tests liquid coolant samples for bacteria. The test is a heterotrophic plate count (HPC) that follows ASTM D8516-23, and the result is reported in CFU/mL.

What a heterotrophic plate count is

A heterotrophic plate count measures the bacteria in a fluid that will grow on a culture medium. A measured volume of the sample is plated and incubated, and the colonies that grow are counted. The result is given in colony forming units per milliliter, CFU/mL.

The method

  • Heterotrophic plate count following ASTM D8516-23.
  • IDEXX EasyDisc PCA test.
  • 1 mL of the sample is plated.
  • Incubation for 48 hours at 35 °C.
  • Designed for counts between 10 and 300 CFU/mL.

Why bacteria in coolant matter

Bacteria that grow in a cooling loop can form deposits that restrict small passages and load filters. A bacteria count shows whether the fluid is under control when it is filled and while it is in service.

Sample handling

A bacteria count changes while a sample sits in a bottle. Bacteria can grow in a stagnant sample, and temperature extremes in shipping can kill them. The sooner the test starts after sampling, the closer the result is to the condition of the system.

  • Use a separate, sealed bottle for the bacteria sample.
  • Write the sampling date and time on it.
  • Ship it the day it is pulled, by the fastest service available.

What the report contains

  • The bacteria count in CFU/mL.
  • The method used.

Related testing

Particles in the same fluid are counted and sized as a separate test. See glycol coolant particle testing. SEM-EDS analysis identifies what the particles are made of.

Requesting a test

To quote it, we need:

  • The fluid type.
  • The number of samples.
  • Your bacteria limit, if you have one.

Ship samples to Industrial Inspection Company, 399 Detroit Avenue, Monroe, Michigan 48162. Call +1 (734) 242-9935, email sales@oemsupplier.com, or use the contact form.

Frequently asked questions

Colony forming units per milliliter. It is the number of bacterial colonies that grew from one milliliter of the sample.

The plates incubate for 48 hours, so a count is available no sooner than two days after the test starts.

The method is designed for counts between 10 and 300 CFU/mL.

The test plates 1 mL. Send a small, sealed bottle used only for the bacteria sample.

Bacteria can grow or die in a bottle during transit. A sample tested soon after it is pulled gives a result closer to the condition of the system.

Talk to an Expert – Get Answers Now.